Schneider Circuit breaker Compact NSX100B, 25 kA at 415 VAC, TMD trip unit 63 A, 3 poles 3d LV429552
Range : ComPact
product name : ComPact NSX
range of product : ComPact NSX100…250
device short name : NSX100B
product or component type :Circuit breaker
device application : Distribution
Number of poles :3P
protected poles description:
3t
[In] rated current
63 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
network type
AC
network frequency
50/60 Hz
suitability for isolation
Yes conforming to EN/IEC 60947-2
utilisation category
Category A
[Icu] rated ultimate short-circuit breaking capacity
15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Performance level
B 25 kA 415 V AC
trip unit name
TM-D
trip unit technology
Thermal-magnetic
trip unit protection functions
LI
control type
Toggle
Circuit breaker mounting mode
Fixed
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service short-circuit breaking capacity
20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability
50000 cycles
electrical durability
10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
mounting support
Backplate
upside connection
Front
downside connection
Front
connection pitch
35 mm
protection type
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
trip unit rating
63 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable
[Ir] long-time protection pick-up adjustment range
0.7…1 x In
Long-time protection delay adjustment type tr
Fixed
[tr] long-time protection delay adjustment range
120…400 s at 1.5 x In
15 s at 6 x Ir
Short-time protection pick-up adjustment type Isd
Fixed
[Isd] Short-time protection pick-up adjustment range
500 A
Short-time protection delay adjustment type tsd
Fixed
earth-leakage protection
Without
Number of slots for electrical auxiliaries
5 slot(s)
Width (W)
105 mm
Height (H)
161 mm
Depth (D)
86 mm
net weight
2.05 kg
Environment
standards
EN/IEC 60947
product certifications
CCC
EAC
Marine
overvoltage category
Class II
electrical shock protection class
Class II
pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
ambient air temperature for operation
-25…70 °C
ambient air temperature for storage
-50…85 °C
relative humidity
0…95 %
operating altitude
0…2000 m without derating
2000 m…5000 m with derating
Mention 800buildingmaterials when calling supplier to get a BEST DEALS